UPS Battery

Model PQ4LN01,5,10-D

Precision Split Current Transformers

 Low Input Amps with Low Voltage Output 0.4" Window:

                                                                                                    

Ø     Accuracy 0.5%

Ø     Phase Shift <60' Typical

Ø     Removable Leg - Easy To Install               

Ø     1A, 5A, 10A  Ranges

Ø     Wide Bandwidth 50Hz to 1KHz

Ø     Excellent Low Current Sensitivity

Ø     ETL Recognized per UL506

Ø     Comes with D-BMI TR type connector

 

PQ4LN is an indoor type CT. An internal voltage setting resistor sets the full scale output voltage to 1500 mV to be compatible with D-BMI instruments- this resistor also provides open circuit shock protection.

 The removable leg contains a lapped spring loaded core that mates with the precision core in the main housing. The phase displacement is adjusted to be within +/-60'.

 

Input Current: 50/60Hz sinewave or distorted sinewave, single phase

Power Factor: Any load power factor from 0.5 to 1.0 either lead or lag

Voltage Rating: 600VAC -- tested per UL506

Interface Impedance: Minimum of 100,000 Ohms resistive (negligible loading)

Output:  1500 Millivolts AC for full scale 1,5,10 amps

Ratio/Linearity Accuracy:  0.5%  <0.1% available on special order>

Phase Displacement or Shift:  60' or less @ 50/60Hz

Phase Connection Relationship: White wire positive with arrow towards source

Bandwidth: 50Hz to > 1KHz within 3db

Temperature Affects: Less than 0.05% deviation in output voltage from -20ºC TO +50ºC

Construction: Plastic ABS/PVC UL94-VO ; removable leg uses 2 knurled nylon screws. Twisted pair of leads 2 meters long to D-BMI TR connector. Compatible with new portables and 61000 instruments.

 

PQ4LN01-D   10 ma to 1000 ma  over range to 5 amps

PQ4LN05-D   100 ma to 5.0 a  over range to 25 amps

PQ4LN10-D   100 ma to 10 a  over range to 200 amps

 

Order from :  info@powerquality.org

Power Quality Inc,

642 E 39th Placs, #5

Yuma, AZ 85365

1-928-344-9008 fax 1-928-344-8847

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 


Home | Locations | More About Us | Products | PQFAQs  | Power Quality Request Form

Last Revised 08/17/10 - 1998 Power Quality Inc. -  All rights reserved

email.gif (25129 bytes)

info@powerquality.org

We gladly accept